Compound F2-I
Radiation crosslinkable non-tracking compound for heat-shrinkable
tubings for indoor and outdoor applications up to 33 kV, to permit clearance
reduction, flashover protection against accidential bridging and prevention
of pollution flashover. The compound shows excellent weathering
and non-tracking properties.
Compound properties
Compound F2-I is a radiation crosslinkable compound offering excellent
weathering and non-tracking properties. The carefully selected combination
of polymers, fillers, processing aids and additives makes this non-tracking
compound an excellent choice for the manufacturing of heat-shrinkable
tubings for straight and bent busbars and for use in terminations, railway
catenaries, high voltage switchgears , substations and fuse links.
The compound is easy processable and can be extruded on standard PE or
PVC screws having a 2:1 pressure ratio.
Compound characteristics
| Color |
|
Red |
| Specific gravity |
ASTM D 792 |
1.3 |
| MFI (160șC, 21.6kg) |
ASTM D 1238 |
10 |
| Tracking resistance |
ASTM D 2303-73 |
No tracking, no erosion to top surface, no flame failure after:
- 1 hr. @ 2.50 kV
- 1 hr. @ 2.75 kV
- 1 hr @ 3.0 kV
- 20 min.@ 3.25 kV |
Extrusion
| Recommended extrusion temperature profile |
130șC - 135șC - 140șC - 145șC - 150șC |
Crosslinking
| Recommended dose |
60 - 90 kGY |
| Hot-set elongation |
125 - 175% (150șC and 35gr/mm2) |
Packaging
The PTL F2-I compound is packed in PE-bags of 25 kg.
A shelf-life of 12 months is achieved if stored below 30șC.
Tubing properties
Heat-shrinkable tubing made of this compound will show superior non-tracking
characteristics combined with excellent erosion and UV-resistance resulting
in an exceptional long-term performance, confirming the material's reliability.
The flexibility of the tubings made of F2-I compound allow them to be
easily positioned on straight and bent busbars.
The low shrink temperature will result in quick and easy installation.
Technical values
| Property |
Test Method |
Typical value |
| |
| Physical |
| Tensile strenght at break |
ASTM D 638 |
10 MPa |
| Elongation at break |
ASTM D 638 |
400% |
| |
| Thermal |
| Continuous operating temperature |
|
-55șC to +110șC |
| Low temp. flexibility (-40șC) |
ASTM D 2671C |
No cracking |
| Minimum shrink temperature |
|
100șC |
| |
| Chemical |
| Fungus resistance |
|
Inert |
| Fluid resistance |
ESI 09-13 |
Excellent |
| Copper Corrosion |
ASTM D 2671 B |
Excellent |
| |
| Electrical |
| Dielectric strength |
ASTM D 2671 |
10-25 kV/mm(*) |
| Volume resistivity |
ASTM D 257 |
10 @ 14 ohm.cm |
| Erosion |
VDE 0303 Part 1 |
Class KA3c |
International specifications
- ESI 09-13
(*) Depending on wall thickness.
|